Refrigerant Leak Detection Quiz
Ten questions on finding refrigerant leaks and proving the repair. Pick an answer to see whether you are right and why. Related reading: The Code: refrigerant rules.
-
A leak is suspected and the system still holds refrigerant. A sensible first step is to:
- Add refrigerant and leave
- Check likely leak points with an electronic leak detector, then confirm with bubble solution
- Replace the compressor
- Vent the system
Check the usual suspects with a detector and confirm with bubbles. Topping off without finding the leak only delays the next service call.
-
A standing pressure test is normally done with:
- Oxygen
- Dry nitrogen
- Compressed shop air
- Propane
Dry nitrogen is inert and free of moisture. Oxygen can react violently with oil, and shop air brings moisture in with it.
-
During a nitrogen pressure test, the pressure should:
- Never exceed the test pressure the manufacturer specifies for the equipment
- Be as high as the regulator allows
- Be 1 psig
- Be applied without a regulator
Always use a regulator and stay within the manufacturer's test pressure. Too much pressure can damage components or cause injury.
-
Bubble solution is most useful for:
- Pinpointing the exact location of a leak
- Measuring the charge
- Finding leaks inside a coil you cannot reach
- Measuring vacuum
Once you know roughly where the leak is, bubbles show the exact spot. Give it time, because small leaks form foam slowly.
-
Common leak points on residential systems include:
- Schrader valve cores, flare nuts, service valves, evaporator coils and lines rubbed through by vibration
- Thermostat wires
- Air filters
- The blower wheel
Mechanical connections, valves and spots where copper vibrates against metal are frequent leak points. Evaporator coils can also develop corrosion leaks.
-
Formicary corrosion is:
- Corrosion in copper tubing, often in evaporator coils, that causes tiny pinhole leaks
- Rust on the outdoor cabinet
- A thermostat fault
- Oil breakdown
Formicary corrosion eats tiny tunnels through copper and has been linked to certain organic acids in indoor air. The leaks are very small and hard to find.
-
An ultrasonic leak detector works by:
- Detecting the high-frequency sound of gas escaping from a pressurized leak
- Sensing refrigerant chemicals
- Measuring temperature
- Using ultraviolet light
It listens for the hiss of escaping gas, so it works with any pressurized gas, nitrogen included. Background noise makes it harder to use.
-
UV dye leak detection:
- Shows leaks as glowing spots under a UV light, but only use a dye the equipment manufacturer allows
- Works without any light source
- Is required on every system
- Seals leaks permanently
The dye travels with the oil and shows at the leak under UV light. Some manufacturers restrict additives, so check before you add anything.
-
An electronic leak detector alarms near a joint. The best practice is to:
- Confirm the exact spot with bubble solution before repairing
- Add refrigerant right away
- Trust it completely
- Turn it off
Electronic detectors can false-alarm on other vapors and drafts. Bubbles confirm the exact location before you cut or braze.
-
After repairing a leak on a system that was opened, the right sequence is:
- Pressure test, evacuate to the required vacuum, then recharge by weight
- Recharge immediately without evacuating
- Top off until the pressure looks right
- Run the system without gauges and see
Prove the repair is leak-free, dry the system with a deep vacuum, then weigh in the correct charge and verify it.