Checking the Charge Quiz
Ten questions on superheat, subcooling and verifying a refrigerant charge. Pick an answer to see whether you are right and why. Related reading: The Code: charging.
-
On a system with a fixed orifice (piston) metering device, which method is normally used to check the charge?
- Subcooling
- Superheat
- Amp draw only
- Sight glass
A fixed orifice cannot adjust, so superheat changes with the charge. Charge to the target superheat from the manufacturer's chart or a target superheat calculator.
-
On a system with a TXV, which method is normally used?
- Superheat
- Subcooling
- Suction pressure only
- Discharge temperature
A TXV holds superheat steady on its own, so superheat no longer reflects the charge. Charge to the subcooling on the data plate or in the installation instructions.
-
Target superheat for a fixed orifice system is based on:
- Indoor wet bulb and outdoor dry bulb temperature
- Outdoor wet bulb and indoor dry bulb temperature
- Supply air temperature only
- The compressor's amp draw
Indoor wet bulb reflects the load on the evaporator and outdoor dry bulb reflects the condensing conditions. Together they set the target superheat.
-
Before adjusting the refrigerant charge, what should you confirm first?
- Correct indoor airflow and clean coils
- The thermostat brand
- That the outdoor unit is level
- The age of the system
Low airflow or dirty coils change pressures and temperatures and make a correctly charged system look wrong. Fix airflow first, then check the charge.
-
Roughly how long should a system run before charge readings are reliable?
- 30 seconds
- 2 minutes
- 10 to 15 minutes
- 2 hours
Pressures and temperatures need time to settle under a steady load. Readings taken right after startup are misleading.
-
High superheat and low subcooling on a TXV system most likely point to:
- Overcharge
- Undercharge
- Too much indoor airflow
- A dirty condenser
With too little refrigerant the evaporator is starved, so superheat rises, and little liquid is stacked in the condenser, so subcooling falls.
-
High subcooling and high head pressure on a TXV system with a clean condenser and normal airflow most likely point to:
- Undercharge
- Overcharge
- Low indoor airflow
- A weak run capacitor
Extra refrigerant stacks up as liquid in the condenser, which raises both subcooling and head pressure.
-
Where should the line temperature for superheat be measured?
- On the liquid line near the condenser
- On the suction line, close to the service valve where the suction pressure is read
- On the discharge line
- In the return air
Measure the line temperature close to where the pressure is taken, with a clamp or probe that is insulated from the outdoor air.
-
When a system has been evacuated and is being charged from empty, the most accurate method is to:
- Charge by suction pressure
- Weigh in the factory charge plus the line-set adjustment, then verify
- Charge until the suction line sweats
- Charge until the compressor amps match the nameplate
A scale gives the exact amount. Superheat or subcooling then confirms it once the system is running.
-
Superheat well below target on a fixed orifice system with normal airflow usually means:
- Undercharge
- Overcharge
- A restricted filter drier
- A very high indoor wet bulb
Too much refrigerant floods the evaporator, so the vapor leaving it barely warms above saturation. Very low superheat risks liquid reaching the compressor.