Vacuum Pump Procedure Quiz
Ten questions on evacuation, micron gauges and decay tests. Pick an answer to see whether you are right and why. Related reading: The Code: vacuum.
-
The main reasons to evacuate a system are to remove:
- Oil and refrigerant
- Air (non-condensables) and moisture
- Dust and debris
- Flux and solder
Non-condensables raise head pressure, and moisture forms acids and can freeze at the metering device. A deep vacuum boils the moisture off and pulls the air out.
-
Vacuum depth is measured accurately with:
- The low-side compound gauge
- A micron gauge
- A thermometer
- A clamp meter
A compound gauge cannot resolve such low pressures. A micron gauge reads in microns of mercury, and 1,000 microns is one millimeter of mercury.
-
Where should the micron gauge be connected for the most accurate reading?
- At the vacuum pump
- At the system, as far from the pump as practical
- On the refrigerant cylinder
- It does not matter
At the pump, the gauge reads the pump's vacuum, not the system's. At the far end of the system it shows what the system has actually reached.
-
Removing the Schrader valve cores during evacuation:
- Slows the process down
- Greatly speeds evacuation by removing a major restriction
- Is not allowed
- Lets air into the system
Valve cores and their depressors restrict flow. Pull them with a core removal tool that keeps the system sealed, and use short, large-diameter hoses.
-
A common target that many manufacturers specify for a deep vacuum is:
- 5,000 microns
- 2,000 microns
- 500 microns or lower
- 29.92 inches of mercury on a compound gauge
Many installation instructions call for 500 microns or lower, followed by a decay test. Use the manufacturer's value for the equipment.
-
After the pump is isolated, the micron reading rises quickly and keeps climbing without leveling off. This usually indicates:
- A leak
- A normal result
- Too much oil
- A completely dry system
A steady, continuous rise means air is getting in. Find the leak with a nitrogen pressure test.
-
After the pump is isolated, the reading rises and then levels off. This usually indicates:
- A leak
- Moisture or outgassing still in the system
- A perfect vacuum
- A failed micron gauge
Moisture keeps boiling off until the pressure reaches its vapor pressure, then the rise stops. Keep evacuating until the reading holds.
-
Before pulling a vacuum on a new installation, the system should be:
- Pressure tested with dry nitrogen to confirm it is leak-free
- Charged with refrigerant
- Run for an hour
- Left open to the atmosphere
A standing nitrogen pressure test finds leaks quickly and safely. Pulling a vacuum on a leaking system wastes time.
-
Why change vacuum pump oil often?
- Oil contaminated with moisture limits how deep the pump can pull
- Old oil changes the refrigerant type
- Only to make the pump quieter
- Manufacturers require it every ten years
Moisture and contaminants in the oil reduce how deep the pump can pull. Fresh oil keeps it working properly.
-
After evacuation, the vacuum should be broken with:
- Outdoor air
- The system's refrigerant or dry nitrogen
- Compressed shop air
- Oxygen
Air puts moisture and non-condensables straight back in. Never use oxygen in a refrigerant system, because it can react violently with oil.