THE CODE

The rules every HVAC tech works by

Every reading on your gauges has a rule behind it. Superheat tells you how the evaporator is being fed. A micron gauge tells you whether moisture is still in the system. A cylinder of R-454B comes with different rules from a cylinder of R-410A, and some of those rules are federal regulation, not just a line in the manual.

This page collects those rules in one place: what they are, why they exist and where they come from. Where a rule comes from a regulator or a public agency, the source is linked. Where it comes from the equipment, the manufacturer's instructions win. At the bottom are 14 free practice quizzes, one for each topic.

01

Charge to the metering device, never to a pressure

A suction pressure on its own tells you very little. Superheat and subcooling tell you how the refrigerant is behaving in the coil, and which one you trust depends on how the evaporator is fed.

Pressure is a temperature in disguise. Inside the evaporator and the condenser the refrigerant is boiling or condensing, so the pressure you read converts straight to a saturation temperature. What you need to know is how far the real line temperatures sit from those saturation points. Superheat is how far the suction line has warmed past the evaporator's saturation temperature. Subcooling is how far the liquid line has cooled below the condenser's saturation temperature.

Which reading sets the charge depends on the metering device. A fixed orifice or piston cannot adjust, so superheat moves with the charge, and you charge to a target superheat worked out from indoor wet bulb and outdoor dry bulb. A TXV or EEV holds superheat steady on its own, so on those systems superheat stops telling you about the charge. You charge them to the subcooling on the unit's data plate or in its installation instructions.

Two things come before any charge adjustment. Airflow has to be right, because a dirty filter or a slow blower drops suction pressure and makes a correctly charged system look short. And the system has to run long enough to settle, usually ten to fifteen minutes under a steady load, before any reading means much. Charge a system with low airflow and you will overcharge it.

When a system has been opened, evacuated and is being charged from empty, weigh the charge in: the factory charge plus the line-set adjustment from the installation instructions. Then confirm it with superheat or subcooling once it is running. The scale is exact. The readings are the confirmation.

02

Pressure and temperature move together, until they don't

A PT chart only applies where liquid and vapor exist together. Knowing where that is, and where it isn't, is the difference between a reading and a guess.

Inside the evaporator and condenser, refrigerant is a saturated mix of liquid and vapor, and its pressure fixes its temperature. That is why a gauge reading converts to a temperature on a pressure-temperature chart. R-410A boils at 40°F at about 118 psig. R-22 boils at the same 40°F at only about 69 psig.

Outside the coils the rule breaks. The suction line carries superheated vapor and the liquid line carries subcooled liquid, so neither line's temperature can be read off the chart. That is exactly why superheat and subcooling exist: they measure the gap between the real temperature and the saturation temperature the pressure predicts.

Blends add a wrinkle. R-454B has a small temperature glide, so it boils across a narrow range of temperatures instead of at a single point. Use the dew point values for superheat and the bubble point values for subcooling, or let a digital manifold set to the correct refrigerant do the conversion.

A PT chart also tells you something before you touch a tool. A system that has been off long enough to settle should read close to the saturation pressure for the surrounding temperature. Well below it suggests there is little liquid left in the system. Above it points to non-condensables or the wrong refrigerant.

03

A vacuum is a moisture test, not a timer

Evacuation boils off water and pulls out air. The micron gauge, not the clock, tells you when it is done.

Air and moisture are the two things a sealed system cannot tolerate. Non-condensable gases raise head pressure. Moisture reacts with refrigerant and oil to form acids and sludge, and it can freeze at the metering device. Pulling a deep vacuum lowers the pressure so far that water boils at room temperature and leaves as vapor.

Measure it with a micron gauge connected at the system, as far from the pump as practical, not at the pump itself. A pump can read deep while the system is still wet, because the hoses and valve cores between them choke the flow. Pull the Schrader cores with a core removal tool and use short, large-diameter hoses, and the job goes several times faster.

Many manufacturers call for 500 microns or lower. Then comes the part that matters most: isolate the pump and watch the gauge. A reading that rises a little and levels off is moisture still giving off vapor, so keep pulling. A reading that climbs steadily without stopping is a leak, and no amount of pumping will fix it. Find it first with a standing nitrogen pressure test.

Break the vacuum with the system's refrigerant or with dry nitrogen, never with air. Change the vacuum pump oil often, because oil that has absorbed moisture limits how deep the pump can pull.

04

Airflow comes first, every time

Many refrigerant-side symptoms have an airflow cause. A system cannot move heat that never reaches the coil.

A typical cooling system is designed around roughly 350 to 450 cubic feet per minute of air for each ton of capacity, with 400 CFM per ton the usual starting point. Humid climates often run lower to pull more moisture out of the air. The manufacturer's data and the design load set the real number for a given system.

When indoor airflow drops, the evaporator gets less heat to absorb. Suction pressure and coil temperature fall, superheat on a fixed orifice drops, and on a bad enough day the coil freezes solid. A tech who reads that as a low charge and adds refrigerant has now overcharged a system whose real problem was a dirty filter.

The usual causes are simple: a clogged filter, a dirty evaporator coil, closed or blocked registers, a crushed or undersized duct, a blower speed set too low, or a blower wheel caked with dust. Total external static pressure, measured across the air handler with a manometer, shows how hard the blower is working against the duct system and is the quickest way to tell a duct problem from an equipment problem.

The Department of Energy puts a number on the simplest fix: replacing or cleaning a dirty filter can lower an air conditioner's energy use by 5 to 15 percent. Check airflow before you connect a single gauge.

2014Energy Saver: Home Cooling 101U.S. Department of Energy

DOE's guide to home cooling. It puts the saving from replacing or cleaning a dirty air filter at 5 to 15 percent of an air conditioner's energy use, and notes that a clogged filter restricts airflow and lowers efficiency.

View on U.S. Department of Energy →

05

Refrigerant handling is federal law

Section 608 of the Clean Air Act decides who may open a refrigerant circuit, what has to happen to the refrigerant, and what can never be done with it.

Under Section 608, technicians who maintain, service, repair or dispose of stationary equipment that could release refrigerant must be certified. EPA issues four types: Type I for small appliances, Type II for high- and very high-pressure appliances, Type III for low-pressure appliances, and Universal for all of them. Most residential and light commercial air conditioning falls under Type II.

Intentionally venting refrigerant while servicing, repairing or disposing of equipment is prohibited, and that covers the HFC substitutes as well as the older ozone-depleting refrigerants. The narrow exception is the de minimis release that happens during good-faith recovery, such as connecting and disconnecting hoses. Everything else is recovered with certified recovery equipment before a system is opened or scrapped.

Recovery cylinders are painted gray with a yellow shoulder. Never fill one past 80 percent of its capacity: liquid refrigerant expands as it warms, and a full cylinder has nowhere for it to go. Weigh the cylinder while you fill instead of guessing, keep one refrigerant per cylinder, and check the retest date stamped on the shoulder before you use it.

These rules apply whatever the size of the job. A rooftop unit and a window unit are both covered; only the certification type and the recovery requirements differ.

Verified November 2026Types of Technician CertificationU.S. Environmental Protection Agency

EPA's definitions of the four Section 608 certification types: Type I for small appliances, Type II for high- and very high-pressure appliances, Type III for low-pressure appliances and Universal for all equipment.

View on U.S. Environmental Protection Agency →
Updated December 2025Prohibition on Venting RefrigerantsU.S. Environmental Protection Agency

The Section 608 rule against intentionally venting ozone-depleting refrigerants or their substitutes during service, repair or disposal, and the limited de minimis exception for releases made during good-faith recovery.

View on U.S. Environmental Protection Agency →
2000Refrigerant Recovery Compliance and SafetyThe ACHR News

A trade explainer on recovery practice: recovery cylinders painted gray with a yellow shoulder under DOT rules, the 80 percent fill limit, and periodic retesting of refillable cylinders with the test date stamped on the shoulder.

View on The ACHR News →

06

A2L refrigerants change the rules at the cylinder

R-32 and R-454B are now in most new residential systems. Both are classed as lower toxicity and lower flammability, and that changes your tools, your cylinders and your habits.

Since January 1, 2025, new residential and light commercial air conditioners and heat pumps made or imported for the US market have had to use a refrigerant with a global warming potential below 700, under EPA's Technology Transitions rule. That took R-410A out of new equipment, and most manufacturers moved to R-32 or R-454B.

In May 2026 EPA removed the January 1, 2026 installation deadline for systems built or imported before 2025, so existing R-410A equipment can still be installed until that inventory runs out. The rule never stopped anyone from servicing an existing R-410A system.

Both new refrigerants carry the A2L safety class: lower toxicity and lower flammability. They are hard to ignite and burn slowly, but they can burn. Keep ignition sources away from an open circuit, ventilate the work area, and use recovery machines, vacuum pumps and leak detectors rated for A2L refrigerants. A2L cylinders have left-hand threaded valves, so your adapters and hoses have to match.

Equipment designed for A2L refrigerants is listed to UL 60335-2-40, which can require a refrigerant detection system that senses a leak and responds, typically by running the indoor blower to dilute the refrigerant. Never bypass one, and follow the manufacturer's instructions for testing and replacing the sensor.

Updated August 2026Technology Transitions HFC Restrictions by SectorU.S. Environmental Protection Agency

EPA's sector tables. Residential and light commercial air conditioning and heat pump products and systems carry a GWP limit of 700, with a January 1, 2025 compliance date, and no installation compliance date for systems whose components were made or imported before 2025.

View on U.S. Environmental Protection Agency →
May 2026Technology Transitions Final Rule Fact SheetU.S. Environmental Protection Agency

EPA's summary of the 2026 changes. It removes the January 1, 2026 installation compliance date for residential and light commercial systems above the 700 limit that were manufactured or imported before January 1, 2025, so that inventory can be installed until it runs out.

View on U.S. Environmental Protection Agency →
Verified November 2026A2L Refrigerants: Fire Service HandoutIllinois Office of the State Fire Marshal

A plain-language sheet on A2L refrigerants: lower toxicity and lower flammability, with R-32, R-454B and R-1234yf as examples, and the leak detection system that forms part of the UL 60335-2-40 listing for HVACR equipment.

View on Illinois Office of the State Fire Marshal →

07

Every system runs on a 24-volt conversation

The thermostat does not power anything. It closes switches on a 24-volt circuit, and every safety on that circuit gets a vote.

A step-down transformer supplies about 24 volts AC to the control circuit. The thermostat is a set of switches that connects R, the 24-volt supply, to whichever terminal is calling: G brings on the indoor fan, Y the compressor contactor, W the heat, and on a heat pump O or B drives the reversing valve. C is the common side of the transformer, the return path that also powers the thermostat itself.

Safety switches sit in series on that circuit: high- and low-pressure switches, the condensate float switch, door switches and limits. When one opens, the call never reaches the equipment, which is why so many no-cool calls end at a tripped float switch and a full drain pan.

Troubleshoot it with a meter, one point at a time. Confirm 24 volts between R and C at the control board, then follow the call. With Y calling, you should see 24 volts from Y to C at the outdoor unit. A switch in series that reads 24 volts across its own terminals is open; a closed switch reads close to zero. A blown 3- or 5-amp fuse on the board means something shorted the low-voltage wiring, so find the short before you replace the fuse.

Wire colors are a convention, not a rule. Red, white, green, yellow, blue and orange are common, but the terminal letter is what counts. Label every wire before you disconnect it.

08

Gas heat is a combustion appliance first

A furnace is a controlled fire inside a house. The ignition sequence, the venting and the combustion test exist because the worst failure is invisible.

A modern furnace lights in a fixed order. The thermostat calls on W. The control board starts the inducer, the pressure switch proves draft, the hot surface igniter heats, the gas valve opens and the flame sensor proves flame within a few seconds. After a delay the blower starts. If any step fails, the board shuts down and usually flashes a code, and the step where it stopped is where you start troubleshooting.

Flame proving works by flame rectification: the flame conducts a tiny DC current, measured in microamps, from the sensor to ground. A dirty or poorly grounded sensor reads low, and the furnace lights, runs a few seconds and shuts off.

Carbon monoxide is why combustion testing matters. CDC counts more than 400 Americans killed each year by unintentional carbon monoxide poisoning not linked to fires, more than 100,000 emergency department visits and more than 14,000 hospitalizations, and it lists gas- and oil-burning furnaces among the common sources. CO has no color and no smell.

Use a combustion analyzer to check CO, oxygen and flue temperature, and verify manifold gas pressure and temperature rise against the furnace's rating plate. Check the venting for the appliance's category, look for flame rollout and signs of a cracked heat exchanger, and make sure the home has working CO alarms.

Verified November 2026Carbon Monoxide Poisoning BasicsCenters for Disease Control and Prevention

Each year more than 400 Americans die from unintentional carbon monoxide poisoning not linked to fires, more than 100,000 visit an emergency department and more than 14,000 are hospitalized. Gas- and oil-burning furnaces are listed among the common household sources.

View on Centers for Disease Control and Prevention →

09

Test yourself: 14 practice quizzes

Ten questions each, with the reasoning behind every answer. Free, no account, nothing to install.

Know the reason, not just the number

Every number on this page has a reason behind it. Memorize the number and you can follow a procedure. Understand the reason and you can tell when the procedure does not fit the system in front of you.

Field Notes goes deeper on each topic, one service call at a time.

Read Field Notes